Motor Starting Current Calculator
Estimate the starting (inrush) current of a three-phase AC motor from its horsepower, voltage and efficiency for a direct-on-line, star-delta or soft start. Useful when sizing starters and contactors and checking voltage dip.
Last updated: September 2026
Starting Current
71.8 A
Formula below · 1 source (ecmweb.com) · Updated Sep 2026
Compare with similar
About this calculator
The full-load current (FLA) of a three-phase motor is derived from its mechanical power output converted to electrical input power, then divided by the three-phase power relationship. The formula used is: I = round((HP × 746) / (√3 × V × (η / 100) × 0.85) × 10) / 10, where HP × 746 converts horsepower to watts, √3 ≈ 1.732 comes from the three-phase power relation P = √3 × V(line-to-line) × I × PF, V is line-to-line voltage, η is motor efficiency as a decimal, and 0.85 is a typical power factor for induction motors. Inrush (starting) current is typically 6–8× the FLA for across-the-line starts. A star-delta starter puts ⅓ of line voltage across each winding at start, so it draws ⅓ of the direct-start current (about 2× FLA when direct start is 6×); soft starters are usually set to limit current to about 2.5–4× FLA, and VFDs to about 1–1.5×. For NEC sizing of breakers (up to 250%, NEC 430.52) and conductors (125%, NEC 430.22), use the full-load current from NEC Table 430.250 rather than this calculated value (NEC 430.6(A)(1)).
How to use
Consider a 10 HP motor running at 460 V with 92% efficiency. Step 1 — full-load amps: FLA = (10 × 746) / (√3 × 460 × (92/100) × 0.85) = 7,460 / 623.1 ≈ 11.97 A. Step 2 — apply the starting method: Direct-On-Line (6× FLA) → starting current = 11.97 × 6 ≈ 71.8 A. Star-Delta (2×, a third of the direct-start current) would draw ≈ 23.9 A and a soft starter set to 3× ≈ 35.9 A. Size contactors, fuses and inrush-withstand ratings for the starting current, not just the FLA.
Frequently asked questions
How do I calculate starting inrush current for an electric motor?
Inrush current is the large surge of current drawn when a motor first starts, before the rotor reaches operating speed. For a direct across-the-line start, inrush is typically 6–8 times the full-load amperage (FLA). If your motor has an FLA of 12 A, expect 72–96 A at startup. This is why motor branch-circuit breakers are sized at 250% of FLA — they must tolerate the inrush without tripping. Soft starters typically limit it to about 250–400% of FLA by ramping up the voltage, and variable frequency drives (VFDs) to about 100–150% by ramping up the frequency.
What size circuit breaker do I need for a three-phase motor?
NEC 430.52 and Table 430.52(C)(1) set the maximum rating of the branch-circuit short-circuit and ground-fault protective device: 250% of the motor's full-load current for an inverse-time breaker on a typical three-phase induction motor. Take the full-load current from NEC Table 430.250 (not the nameplate or this estimate) and multiply by 2.5; if that is not a standard size, the next standard size up is allowed (430.52(C)(1) Exception No. 1). For example, Table 430.250 lists 14 A for a 10 HP, 460 V motor: 14 × 2.5 = 35 A, a standard size. Higher ratings are permitted where the motor will not start, and the local code and a licensed electrician have the final say.
Why does power factor affect motor current calculations?
Power factor (PF) represents how efficiently a motor converts apparent power (kVA) into real working power (kW). An induction motor with a PF of 0.85 draws 1/0.85 ≈ 17.6% more current from the supply than it would if PF were 1.0. This extra current does no useful mechanical work but still heats conductors and loads the utility transformer. That is why PF appears in the denominator of the FLA formula — lower PF means higher current for the same horsepower output. Power factor correction capacitors can be added at the motor terminals to reduce this penalty and lower energy costs.
Related calculators
Sources & references
Think a result is wrong? Report a problem with this calculator.